Products | P7099, Encore Wire

4/0-4/0-2/0-4 AWG, Stranded, Aluminum Conductor Mobile Home Feeder Cable, 500' Reel

by: Encore Wire

Locke# P7099 | Mfg# 380392101440
P7099

4/0-4/0-2/0-4 AWG, Stranded, Aluminum Conductor Mobile Home Feeder Cable, 500' Reel

by: Encore Wire

Locke# P7099 | Mfg# 380392101440

For pricing and availability please Sign In

*Item only available: AR, KS, MO, OK, TX, VA

  • Product Featuresarrow_drop_down
    • Two black triple-rated USE-2/RHH/RHW-2 phase conductors cabled together with one white triple-rated USE-2/RHH/RHW-2 neutral conductor and one green insulated ground wire.
    • All cables employ ASTM 8000 Series aluminum alloy conductors.
    • Superior weather, abrasion, crush, and sunlight-resistant XLPE insulation.
    • Manufactured and tested according to ANSI/ICEA S-105-692: Standard for 600-Volt Single Layer Thermoset Insulated Utility Underground Distribution Cables.
    • Also manufactured and tested according to UL-854, and UL-44.
    • Conductors are surface printed for identification.
    • Construction:
    • Conductors:
    • Compact Stranded Conductors, Aluminum Alloy 8000 Series per ASTM B800; ASTM B801; ASTM B836.
    • Insulation:
    • Cross-link polyethylene (XLPE) insulation per UL 854, UL 44, and ANSI/ICEA S-105-692.
    • Black XLPE insulation on phase conductors, white XLPE on neutral conductor, green XLPE on ground.
    • Applications:
    • Quadruplex type USE-2/RHH/RHW-2 with Compact Stranded Aluminum Alloy 8000 Series conductors per ASTM B800; ASTM B801; ASTM B836.
    • Suitable for electrical connections in mobile homes for permanent wiring according to the 2008 NEC.
    • Suitable for wet and dry locations in conduit where temperatures do not exceed 90 C.
    • Direct Burial in earth permitted for Type USE-2, RHH, and RHW-2 per UL854 where temperatures do not exceed 90 C. 600 volt rated. XLPE insulation is sunlight-resistant for 6 AWG and larger.
    • 1/0 AWG and larger complies with IEEE 1202/UL FT-4 flame test.
    • 1/0 AWG and larger also complies with ICEA T-29-520 (210,000 btu/hr) flame test.
    • Standards:
    • Underwriters Laboratories Standards UL-854; UL-44; ANSI/ICEA S-105-692; IEEE 835-1994; Compact Stranded Aluminum Alloy 8000 Series per ASTM B800; ASTM B801; ASTM B836; ARRA 2009 Section 1605 Buy American Compliant.