Elimination of sharp edges by hemming the flue and casing
Assembly and disassembly, without tools, using positive twist-lock
360 deg rotation of small dia fittings using swivel tees, wyes, and elbows
Space savings inside standard stud walls using oval pipe
The vent shall be of the double-wall, factory-built type for use with approved category I appliance burning natural or LP gas, which produce flue gases exhausted at temperatures not exceeding 550 deg F
The vent shall be constructed of an outer wall of galvanized steel 0.018 in thk G-90 for sizes 3 to 14 in Dia and 0.024 in thk G-90 for sizes 16 to 30 in Dia
The inner wall shall be constructed of aluminum alloy 0.012 in thk for sizes 3 to 8 in Dia and 0.018 in thk for sizes 10 to 30 in Dia
The vent pipe shall incorporate a push-tab locking system to prevent disassembly of vent during or after installation
Vent shall be tested and listed for a min clearance to combustibles of 1 in for sizes 3 to 24 in Dia and 2 in for sizes 26 to 30 in Dia
B-Vent shall be installed in accordance with the vent manufacturer's installation instructions, UL listing and state or local codes
Type B-Vent shall be warranted by the manufacturer against defects in material and workmanship for a period of one (1) year from the date of the original installation
Air insulation
Vent overlaps 1.5 in when joined together
B-Vent products shall be listed to UL-441 and carry the appropriate UL or cUL listing mark or label